Extinguishing area of ​​fire extinguisher op 4.

The OP-4 fire extinguisher is a portable injection-type powder fire extinguisher.Powder fire extinguisher OP-4is the primary fire extinguishing agent and is intended to extinguish fire in the event of a fire of gaseous, liquid and solid substances. It can also be used to eliminate fires in electrical installations that are under voltage up to 1000 V. It is an integral attribute of vehicles. Designed to be completed in accordance with fire safety regulations. It is an ideal option for a passenger car.

USE AND PLACEMENT OF POWDER FIRE EXTINGUISHER OP-4 INDOORS

Powder fire extinguisher OP-4 should be positioned in such a way that they are protected from direct sunlight, heat flows, mechanical influences and other unfavorable factors (vibration, aggressive environment, high humidity, etc.). They must be clearly visible and easily accessible in case of fire. It is preferable to place fire extinguishers near places where a fire is most likely to occur, along passageways, as well as near exits from the premises. Fire extinguishers should not interfere with the evacuation of people during a fire. To place primary fire extinguishing means in production and warehouse premises, as well as on the territory of protected objects, fire shields (points) must be equipped. In areas saturated with production or other equipment that obscure fire extinguishers, signs and signs of their location must be installed. Signs must be made in accordance with GOST 12.4.026 and located in visible places at a height of 2.0 - 2.5 m from the floor level, taking into account the conditions of their visibility [GOST 12.4.009; 4] The distance from a possible source of fire to the nearest powder fire extinguisher should not exceed 20 m for public buildings and structures; 30 m for premises of categories A, B and C; 40 m - for premises of categories B and D; 70 m - for premises of category D.

Recommended powder fire extinguisher OP-4 install on hanging brackets or in special cabinets and stands. Powder fire extinguisher OP-4 should be located so that the main inscriptions and pictograms showing the order of their activation are clearly visible and face outward or towards the most likely approach to them.

Locking and starting device and cabinet doors (if they are placed in a cabinet) must be sealed

Powder fire extinguisher OP-4 must be installed so that their top is located at a height of no more than 1.5 m from the floor. They can be installed on the floor, with mandatory fixation against possible fall due to accidental impact.

Distance from door to powder fire extinguisher OP-4 should be such as not to interfere with its full opening.

Powder fire extinguishers OP-4 should not be installed in locations where temperatures exceed the temperature range indicated on fire extinguishers.

The use of primary fire extinguishing agents for household and other needs not related to firefighting is not permitted.

Standards for equipping premises with an OP-4 powder fire extinguisher

Maximum protected area, m 2

Fire class

Powder fire extinguisher OP-4

A B C

(flammable gases and liquids)

G, D

1800

Public buildings

Notes

1. To extinguish fires of various classes, powder fire extinguishers must have appropriate charges: for class A - ABC type powder, for classes B, C and E - ALL or ABC type and for class D - type D

2. The ++ sign indicates fire extinguishers recommended for equipping the facilities, the + sign indicates fire extinguishers, the use of which is allowed in the absence of the recommended ones or with appropriate justification, and the sign indicates fire extinguishers that are not allowed for equipping these facilities.

For the maximum area of ​​premises of different categories (the maximum area protected by one or a group of fire extinguishers), it is necessary to provide the number of fire extinguishers of one of the types indicated in Table. 1 or 2 before the ++ or + sign.

USE AND PLACEMENT OF POWDER FIRE EXTINGUISHER ON VEHICLES

To protect vehicles must be used powder fire extinguishers.

Only those fire extinguishers whose design has passed the vibration strength test are allowed to be installed on vehicles.

It is advisable to use multi-purpose powder compositions of the ABSE type as a charge in powder fire extinguishers.

Cars and trucks must be equipped with powder fire extinguishers with a housing capacity of at least 2 liters (type OP-2).

Especially small class buses (such as RAF, Gazelle, etc.) are equipped with at least one fire extinguisher of the type OP-2;

small class buses (PAZ, etc.) - two fire extinguishers OP-2, middle class buses (LAZ, LiAZ, etc.) and other vehicles for transporting people - two fire extinguishers (one in the OP-5 cab, the other in the cabin OP-2).

Tankers for transporting petroleum products and vehicles for transporting dangerous goods must be equipped with at least two fire extinguishers of the OP-5 type: one must be located on the chassis, and the second must be on the tank or in the body with the cargo.

Heavy-duty off-road dump trucks must be equipped with one fire extinguisher of the type OP-5.

Mobile laboratories, workshops and other vehicles such as a van mounted on a car chassis must be equipped with two-liter fire extinguishers of the appropriate type, depending on the class of possible fire and the features of the mounted equipment.

On all vehicles, fire extinguishers must be located in the cab, in close proximity to the driver or in an easily accessible location. It is prohibited to store fire extinguishers in the trunk, body or other places that are difficult to access. Fire extinguishers located outside the cabin should be protected from exposure to precipitation, sunlight and dirt.

The design of the bracket must be reliable to eliminate the possibility of the fire extinguisher falling out of it when the vehicle is moving, as well as in the event of a collision or impact with an obstacle.

MAINTENANCE AND PERIODIC CHECKS OF POWDER FIRE EXTINGUISHER OP-4

Powder fire extinguisher OP-4 Once put into operation, it must be subject to maintenance, which ensures that the fire extinguisher is constantly ready for use and the reliable operation of all components of the fire extinguisher throughout its entire service life.

Maintenance includes periodic inspections, inspections, repairs, testing and recharging of fire extinguishers.

Periodic checks are necessary to monitor the condition powder fire extinguisher OP-4, control of the installation location of the fire extinguisher and the reliability of its fastening, the possibility of free access to it, the presence, location and readability of instructions for working with the fire extinguisher.

Maintenance powder fire extinguisher OP-4 must be carried out in accordance with the operating instructions and using the necessary tools and materials by a person appointed by order of the enterprise or organization, who has passed the test of knowledge of regulatory and technical documents on the design and operation of fire extinguishers and fire extinguisher parameters in accordance with the established procedure, and who is capable of independently carrying out the required amount of work on servicing fire extinguishers.

Powder fire extinguishers OP-4, taken out of service for the period of repair, testing or recharging, must be replaced with backup fire extinguishers with similar parameters.

Before insertion powder fire extinguisher OP-4 before operation, it must be subjected to an initial inspection, during which an external inspection is carried out, the contents of the fire extinguisher and the condition of its installation site are checked (visibility of the fire extinguisher or the indicator of its installation location, the possibility of free access to it), as well as the readability and intelligibility of the instructions for working with the fire extinguisher . During the external inspection, you need to pay attention to:

The presence of dents, chips, deep scratches on the body, control units, nuts and head of the fire extinguisher;

Condition of protective and paint coatings;

Availability of clear and understandable instructions;

Availability of a sealed safety device;

The serviceability of the pressure gauge or pressure indicator (if it is provided for in the design of the fire extinguisher), the presence of the necessary mark and the amount of pressure in the pump-type fire extinguisher or in the gas cylinder;

The mass of the fire extinguisher, as well as the mass of the fire extinguisher in the fire extinguisher (the latter is determined by calculation);

Condition of the flexible hose (if any) and the fire extinguishing agent sprayer (presence of mechanical damage, traces of corrosion, casting burrs or other objects that prevent the free exit of the fire extinguisher from the fire extinguisher);

The condition of the chassis and the reliability of fastening the fire extinguisher body on the cart (for a mobile fire extinguisher), on the wall or in the fire cabinet (for a portable fire extinguisher).

Based on the results of the inspection, the necessary notes are made in the fire extinguisher’s passport, it is assigned a serial number, which is applied to the fire extinguisher and recorded in the fire extinguisher logbook.

Quarterly inspection includes inspection of the installation site powder fire extinguisher OP-4 and approaches to it, as well as conducting an external inspection of the fire extinguisher.

The annual fire extinguisher inspection includes an external inspection powder fire extinguisher OP-4, inspection of the place of its installation and approaches to it. During the annual inspection, the amount of leakage of expellant gas from a gas cylinder or fire extinguisher from a gas fire extinguisher is monitored. The fire extinguishers are opened (full or selective), the condition of the filters is assessed, the fire extinguisher parameters are checked and, if they do not comply with the requirements of the relevant regulatory documents, the fire extinguishers are recharged.

In case of increased fire danger of the facility (premises of category A) or when exposed to powder fire extinguisher OP-4 such unfavorable factors as positive (over 40 °C) or negative (below minus 40 °C) ambient temperature close to the limit value, air humidity more than 90% (at 25 °C), corrosive environment, exposure to vibration, etc. etc., inspection of fire extinguishers and control of fire extinguishers must be carried out at least once every 6 months.

If during the check a discrepancy is detected with any parameter powder fire extinguisher OP-4 requirements of current regulatory documents, it is necessary to eliminate the causes of identified deviations in parameters and recharge fire extinguishers.

At least once every 5 years powder fire extinguisher OP-4 and the cylinder with the expelling gas must be discharged, the fire extinguisher body must be completely cleared of fire extinguisher residues, an external and internal inspection must be carried out, as well as a hydraulic strength test and pneumatic leak testing of the fire extinguisher body, trigger head, hose and shut-off device. During the inspection, you must pay attention to:

Condition of the inner surface of the fire extinguisher body (presence of dents or swellings of metal, peeling of the protective coating);

Presence of traces of corrosion;

Condition of gaskets, cuffs or other types of seals;

Condition of safety devices, filters, pressure measuring instruments, reducers, valves, shut-off devices and their seats;

The mass of the gas cartridge, the period of its next test or the warranty period of the gas-generating element;

Condition of the surface and hose attachment points;

Condition, warranty period of storage and values ​​of the main parameters of the fire extinguishing agent;

Condition and tightness of the container for surfactant or foaming agent (for water and foam fire extinguishers with separate storage of water and other charge components).

If mechanical damage or traces of corrosion are detected, the body and components of the OP-4 powder fire extinguisher must be subjected to a strength test ahead of schedule.

A note about the inspections and tests carried out is made on the OP-4 powder fire extinguisher, in its passport and in the fire extinguisher logbook.

Operating certificate for fire extinguisher

1. Number assigned to the fire extinguisher

2. Date of putting the fire extinguisher into operation

3. Fire extinguisher installation location

4. Type and brand of fire extinguisher

5. Fire extinguisher manufacturer

6. Serial number

7. Date of manufacture of the fire extinguisher

8. Brand (concentration) of charged fire extinguishing agent

Fire extinguisher maintenance results

Date and type of maintenance performed

Appearance and condition of the fire extinguisher components

Total weight of the flamet shitelya

Pressure (if there is a pressure indicator) * or weight of the gas cylinder

Condition of the mobile fire extinguisher chassis

Measures taken to eliminate the noted deficiencies

Position, surname, initials and signature of the responsible person

Fire extinguisher maintenance log

No. and

Maintenance (type and date)

Notes

about technical

Condition

Taken measures

Job title, surname, initials and signature of the person responsible Wow

fire extinguisher brand

Checking the Firet Nodes shitelya

Checking the quality of OTV

Checking the pressure indicator

Resetting the fire extinguisher row

Firet unit testing shitelya

Fire extinguisher testing and recharging log

N and brand of fire extinguisher

Date of testing and recharging; organization that carried out the maintenance living

Resul inspection and test data strength tests

There are a large number of types and modifications of fire extinguishers designed to extinguish a wide variety of fires, the sources of ignition of which can be flammable materials, chemical reactions, etc.

For example, if we take it, it is more compact compared to OP 5 and OP 8. But, accordingly, it contains less extinguishing agent, although OP 4 is in no way inferior to OP 5 in terms of extinguishing time.

This fire extinguisher is less than twice as heavy as the OP 2, which weighs 3.5 kg. It is also almost two times lighter than OP 8, whose weight is 12.0-12.6 kg. Considering its capacity, this mass is optimal for using OP 4 in any office.

How to use it?

In principle, there is nothing easier than learning how to use such a fire extinguisher. First you need to break the seal. After this, you need to remove the pin, which protects the fire extinguisher from accidental activation. Then you should go to the source of the fire, point the bell at it and press the lever.

Enterprises must constantly check that other workers know how to use fire extinguishers, which is very important, since many lives may depend on it.

A fire extinguisher should not be viewed as an overly safe tool, because once a small fire is extinguished, a larger disaster can be prevented.

Powder fire extinguisher OP-4 is designed to extinguish fires of solid, liquid and gaseous substances (class A, B, C or B, C depending on the type of powder used).

Powder fire extinguisher OP-4 is not intended for extinguishing fires of alkali and alkaline earth metals and other materials, the combustion of which can occur without air access.

Technical characteristics of powder fire extinguisher OP-4

Charge weight, kg

Working pressure, MPa

Release length, m, not less

Operating time, sec, not less

Fire extinguishing ability *

Dimensions, mm

Weight, kg, no more

* 1A - combustion of a model hearth in the form of wooden blocks placed in a cube with a volume of 1/8 m³ (2A - volume of the cube is 2 times larger - 1/4 m³, 4A - volume 4 times larger - 1/2 m³, etc. .)

10V - combustion of 10 liters of gasoline with a layer of 3 cm, located in a baking tray shaped like a circle (13V - 13 liters, respectively, 34V - 34 liters, etc.)

How to use a powder fire extinguisher OP-4

Make sure the fire extinguisher is charged (look at the pressure sensor).


Budget price 435 rub.

435 rub.

5 l cylinder

A powder fire extinguisher that is universal in characteristics and volume. Attracts with its price-performance ratio. Suitable for equipping premises, construction sites, vehicles.


An effective fire extinguisher for extinguishing all classes of fires, with the widest range of applications. Fire extinguisher OP-4 can be installed as a primary fire extinguishing agent on cars and trucks, special professional equipment, rural tractors and combine harvesters. OP-4 is suitable for service in most climatic zones - operation is possible at negative ambient temperatures of up to forty degrees. Consequently, the use of fire extinguisher OP-4 (z) for completing panels at construction sites, gas stations, and other street facilities of urban social and commercial infrastructure is not prohibited.

The extinguishing agent is completely released from the cylinder in ten seconds. During extinguishing, it is recommended not to release all the powder at once, but by opening the valve for two to three seconds, distribute the fire extinguisher charge over the entire fire area. According to modern fire safety standards, it is believed that in standard-type premises, one product with a volume of five liters is sufficient for two hundred meters of area. Depending on the class of the object, the number of fire extinguishers may vary.

Serviceability is determined by the reading of the pressure gauge; the indicator must be placed in the green indicator area. If the pressure gauge needle goes into the red zone, the fire extinguisher must be recharged. Pressure gauges are checked annually, throughout their entire five-year service life. The OP-4 fire extinguisher is charged with powder of different qualities, which must be indicated on the label. Cheap powders are not suitable for extinguishing class A fires (wood, cardboard).

Technical characteristics of the fire extinguisher OP-4

The product is certified, the OP-4 fire extinguisher has a mandatory fire safety certificate.

Powder fire extinguishers are the most versatile devices, designed to extinguish almost all classes of fires and used over a wide temperature range. The limitation for their use is fires initiated by the ignition of materials that burn without access to oxygen, for example, alkali or alkaline earth metals.

One of the most popular models of powder fire extinguishers is OP-4 (z) - ABCE. If we decipher this abbreviation, we get: a powder fire extinguisher with a nominal mass of fire extinguishing powder of 4 kg, pumped, intended for extinguishing fires of classes A, B, C and E.

Where is the OP-4 powder fire extinguisher used?

Thanks to the technical parameters and versatility of the fire extinguishing powder, OP-4 is indispensable for extinguishing all types of fires, except for the burning of metals (class D):

  • class A – combustion of solid objects (paper, wood, plastic, etc.);
  • class B – combustion of liquids, both soluble and insoluble in water (gasoline, alcohol, glycerin, etc.);
  • class C – combustion of gases (propane, hydrogen, household gas, etc.);
  • class E – burning of equipment and installations under high current.

Application of OP-4 at such facilities as:

  • public buildings;
  • warehouses;
  • industrial enterprises;
  • household buildings and premises;
  • delivery trucks;
  • minibuses, –

effective and cost-effective, which has been proven in practice.

Technical characteristics of OP-4

Operation of the OP-4 fire extinguisher is possible over a wide temperature range - from minus 40°C to plus 50°C.

The devices need to be recharged once every 5 years, the service life is 10 years.

These powder fire extinguishers are convenient to use, easy to maintain, effective and safe for humans when extinguishing fires.

Technical parameters of OP-4 (z) are as follows:

  1. Capacity – 5 l.
  2. The mass of the explosive charge is 4.0±0.2 kg/l.
  3. Working pressure – 1.4±0.2 MPa.
  4. The duration of powder supply in case of fire is 10 seconds.
  5. Jet length – 3 m.
  6. Cylinder weight – 6 kg. Dimensions – 13 cm diameter, 42 cm height.
  7. Fire extinguishing capacity – 2A (fire class A), 55B (class B).

The principle of exhaust gas release is displacement under the influence of excess pressure, which creates a working gas (carbon dioxide).

How to store powder fire extinguisher OP-4

To store OP-4 indoors, the devices are installed on the floor on special stands or mounted on the wall using brackets. As a rule, the fire extinguisher kit comes with only a hose-socket and a passport for the product, so brackets, stands and other necessary related products are purchased separately.

The location of the OP is selected based on the points of GOST No. 12.4.009. Caring for the OP consists of periodically checking the appearance of the device, the strength of the fasteners, the integrity of the seal, and removing dust and contaminants from the surface.

A more detailed diagnosis of the serviceability of the fire extinguisher is carried out during quarterly maintenance of the device. Once a year, the maintenance company opens the fire extinguisher and evaluates the parameters of the fire extinguisher. Recharging the OP-4 is necessary every 5 years of operation or without fail after activation of the device.

How to activate a powder fire extinguisher OP-4 (z)

In order to activate the OP-4 pump-type fire extinguisher in case of fire, it is necessary to perform the following actions:

  • direct the nozzle from which the extinguishing agent will come out to the source of the fire;
  • break the seal;
  • pull out the fire extinguisher pin, which is a metal rod bent into a ring at the end;
  • press the lever.

After activating the fire extinguisher, begin extinguishing the fire.